Reasons for inaccurate measurement of vortex flowmeter (part 2)

1. The transmitter of the vortex flowmeter stops the abnormal whistling sound:

(1) The flow rate is too high, causing the generator or detection element to vibrate;

(2) Cavitation occurs in the pipeline;

(3) The generating body or detecting element is loose.

Solution: In order to avoid damage to the generating body or detection components, the valve should be adjusted first to reduce the flow rate and the flow rate, and then further investigate the cause.

?

2. Problems in selection. Some vortex sensors have a larger selection due to changes in process conditions after the selection of the caliber or after the design and selection. The actual selection should choose the smallest caliber possible to improve measurement accuracy. For example, a vortex pipeline is designed to be used by several equipment, because some equipment in the process is sometimes not used, resulting in a decrease in the current actual use flow. Actual use causes the original design to select a larger diameter, which is equivalent to an increase in the measurable flow The lower limit is not guaranteed when the process pipeline has a small flow rate, and it can be used when the flow rate is large, because it is sometimes too difficult to rebuild. Changes in process conditions are only temporary.

Solution: It can be combined with the re-tuning of the parameters to improve the accuracy of the indication.

插入式渦街流量計 (2).png

?

3. Reasons for vortex electromagnetic flowmeter parameter setting direction. Due to parameter errors, the indicator indication is wrong. The parameter error makes the calculation of the full scale frequency of the secondary meter wrong. The same full-scale frequency makes the indication inaccurate for a long time, and the actual full-scale frequency is too large. The calculated full-scale frequency makes the indication fluctuate in a wide range and cannot be read. The inconsistency of the parameters in the data affects the final determination of the parameters.

Solution: Finally, the parameters were determined by re-calibration combined with mutual comparison, and this problem was solved.

?

4. The secondary instrument fails. There are many faults in this part, including: there is a disconnection on the circuit board of the instrument, the display of individual digits in the range setting is broken, and the display of individual digits in the K coefficient setting is broken, making it impossible to determine the range setting and K coefficient setting.

Solution: The problem is solved by fixing the corresponding fault.


?

5. The four-way line connection problem. On the surface of some circuits, the circuit connection is very good. Check carefully. Some joints are actually loose and the circuit is interrupted. Although some joints are tightly connected, the fastening screws are fastened to the wire skin due to the secondary line problem, which also makes the circuit Interrupted.

Solution: re-wiring.


插入式渦街流量計 (3).png

6. There is always no indication in the circuit due to the failure of the secondary instrument flat shaft cable. Due to long-term operation, coupled with the impact of dust, the flat axis cable failure.

Solution: The problem can be solved by cleaning or replacing the flat shaft wire.

?

7. Use environmental issues. Especially the part of the sensor installed in the ground well, due to the high humidity in the environment, causes the circuit board to get damp.

Solution: Through corresponding technical improvement measures, some sensors with high environmental humidity were re-processed to separate the probe part from the conversion part, and a separate sensor was used, so the working environment was improved. This part of the instrument is running well recently.

?

8. Due to poor site adjustment, or due to further changes in the actual situation after adjustment. Due to the on-site vibration and noise balance adjustment and sensitivity adjustment is not good. Or due to further changes in the site conditions after a period of operation after adjustment, causing indication problems.

Solution: Use an oscilloscope, and re-adjust according to the process operation.

?

Want to know more about the precession vortex flowmeter, thermal gas mass flowmeter, electromagnetic flowmeter, vortex flowmeter, turbine flowmeter, ultrasonic flowmeter, please pay attention to the official website of Hollysys Industrial Control Instruments.


主站蜘蛛池模板: 建始县| 上饶县| 大同市| 丹寨县| 永济市| 巴南区| 密云县| 兴仁县| 娱乐| 东丰县| 杂多县| 保亭| 泉州市| 柳林县| 峨边| 辉县市| 西宁市| 邻水| 新干县| 保山市| 常德市| 东丽区| 南充市| 湘潭市| 广昌县| 东港市| 游戏| 宁陕县| 利川市| 临西县| 珠海市| 马山县| 辉南县| 铅山县| 五河县| 望江县| 虎林市| 淮安市| 赤壁市| 芦溪县| 任丘市| 定结县| 平湖市| 工布江达县| 酒泉市| 孝昌县| 惠水县| 吴堡县| 朔州市| 高尔夫| 兴化市| 射阳县| 通化市| 保山市| 格尔木市| 金塔县| 图木舒克市| 合川市| 大同市| 垫江县| 乌拉特后旗| 闸北区| 海阳市| 达拉特旗| 济宁市| 寿阳县| 朔州市| 墨江| 工布江达县| 华宁县| 铜鼓县| 嘉义市| 铅山县| 乌什县| 吉水县| 河间市| 德州市| 托克逊县| 威信县| 华池县| 修武县| 马山县|